NXL series tension clamp is suitable for distribution wire up to 10kV, fixing the air-insulated aluminum conductor or bare aluminum conductor to the bend angle or insulator of voltage terminal pole, and then fixing and tightening the antenna conductor.
Product Description:
This is a product designed for use on overhead power lines. Its primary function is to secure or support the conductor while absorbing thermal expansion and contraction due to temperature changes. The NXL series tension clamp consists of three main components: the body, the wedge, and the jacket. The body is the main part of the fixture and the foundation for the other parts. It is made of high-strength aluminum alloy or steel and is designed to withstand the forces that may occur during operation. Secondly, the wedge is made of high-quality synthetic material that has undergone extensive testing for its ability to withstand tension and compression. While the outer jacket is made of high-quality, UV-resistant polymer designed to protect the clamp from environmental factors such as humidity, sunlight, and extreme temperatures. Lastly, our products are manufactured from a variety of high-quality materials selected for performance, durability, and cost effectiveness. This product design reduces the overall cost of the fixture while ensuring that it meets all the necessary requirements. The combination of cost effectiveness, durability and quality ensures that the NXL Series strain gauge clamps offer excellent value for money.
Peculiarity
The most important feature of the NXL series strain gauge clamps is their ability to withstand harsh environmental conditions. The shell is made of high-quality polymer and is designed to protect the clips from extreme temperatures, moisture and UV rays. This ensures that the grip remains safe and secure even in the harshest conditions. In addition, the synthetic wedges that make up the critical part of the clamp are resistant to tension and compression, which means that the clamp will not fail even under very heavy loads. And we also have a unique self-centering feature. This feature ensures that the clamps automatically align after installation, which reduces installation time and minimizes the possibility of installation errors. With the self-centering feature, the clamp is not only reliable, but also easy to install. The fixture can be installed by one person and reduces installation time, optimizing project time. Finally, a versatile, durable and reliable product designed to meet the requirements of overhead power lines. Its unique design features make it ideal for a variety of applications, and its affordability makes it an attractive option for companies looking for a cost-effective solution for overhead network projects.
Application
NXL series tension clamps are widely used in various fields. It is designed to securely fasten and support overhead power lines, ensuring their stability. Using advanced technology and high-quality materials, this clamp is durable and reliable. Easy to install and adjustable design brings convenience and efficiency. It is an important component in the construction and maintenance of power lines, ensuring the safety and stability of the network.
1-10KV specification NXL insulation cover
Stable design catalog No. | Catalog No. | Suitable conductor | Length(mm) | Grip strength(KN) | Specified failure load(KN) | Insulation cover type |
NXL-1 | NXL-1 | 35 | 245 | 3.4 | 7.5 | NXL-95 |
50 | 4.6 | |||||
NXL-2 | 70 | 6.7 | 14.5 | |||
95 | 8.9 | |||||
NXL-3 | NXL-2 | 120 | 255 | 11.3 | 23.4 | NXL-150 |
150 | 13.7 | |||||
NXL-4 | NXL-3 | 185 | 300 | 17.3 | 36.4 | NXL-240 |
240 | 22.5 | |||||
NXL-5 | NXL-4 | 300 | 320 | 28.2 | 61.0 | NXL-4 |
400 | 39.8 |
NXL-J
Catalog No. | Suitable conductor | Length(mm) | Grip strength(KN) | Specified failure load(KN) | Insulation cover type |
NXL-2J | 10KV/35 | Do not peel the insulating layer
| 3.4 | 14.5 | NXL-2J |
10KV/50 | 4.6 | ||||
10KV/70 | 6.7 | ||||
NXL-3J | 10KV/95 | 8.9 | 23.4 | NXL-3J | |
10KV/120 | 11.3 | ||||
10KV/150 | 13.7 | ||||
NXL-4J | 10KV/185 | 17.3 | 36.4 | NXL-4J | |
10KV/240 | 22.5 |
Catalog No. | Suitable conductor | Dia(mm) | Grip strength(KN) | Specified failure load(KN) | Insulation cover type |
NXLJ-1 | LGJ-35/6 | 8.2 | 11.4 | 38 | NXLJ-1 |
LGJ-50/8 | 9.6 | 15.2 | |||
LGJ-70/10 | 11.4 | 21.0 | |||
NXLJ-2 | LGJ-95/15 | 13.6 | 31.5 | 50 | NXLJ-2 |
LGJ-120/7 | 14.5 | 24.8 | |||
LGJ-150/8 | 16.0 | 29.6 | |||
LGJ-185/10 | 18.0 | 36.8 | |||
NXLJ-3 | LGJ-240/30 | 21.6 | 68.0 | 70 | NXLJ-3 |